Richards 15 & 25 kV Elbow Tap Plugs convert a 600A deadbreak interface to a 15 or 25 kV 200A loadbreak interface. The ETP is designed for use with an unthreaded lug and has an internal 3/8″ hex broach for assembly. Once installed, the 200A interface can be used for direct testing & grounding, as well as the addition of 200A loadbreak components.
IEEE 386 – Industry Minimum Requirements | ||
---|---|---|
Voltage Ratings | ||
Voltage Class, Phase-to-Phase | 15kV | 25kV |
Maximum Operating Voltage – (phase-to-ground) | 8.3kV | 15.2kV |
Corona Voltage Level – (partial discharge extinction voltage) | 11kV | 19kV |
AC Withstand – (1 minute) | 34kV | 40kV |
Impulse-Withstand Voltage – (BIL) | 95kV | 125kV |