Deadbreak Reducing Tap Well

Richards kV Reducing Tap Well converts a 600A interface to a 200A well interface.  The tap well can accept either loadbreak or deadbreak inserts for connection to 200A devices.  The P625RTW comes with a molded-in flange for attachment to 200A deadbreak elbows or caps.

IEEE 386 – Industry Minimum Requirements
Voltage Ratings
Voltage Class, Phase-to-Phase 15kV 25kV 35kV
Maximum Operating Voltage – (phase-to-ground) 8.3kV 15.2kV 21.1kV
Corona Voltage Level – (partial discharge extinction voltage) 11kV 19kV 26kV
AC Withstand – (1 minute) 34kV 40kV 50kV
Impulse-Withstand Voltage – (BIL) 95kV 125kV 150kV

 

Continuous Current Ratings
Aluminum 600A
Copper 900A

 

Short-Time Current Ratings
Aluminum 25kA, 10c. and 10kA, 3s.
Copper 40kA, 10c. and 10kA, 3s.
Resource Details

P625RTW

Product Data Sheets

15/25kV Deadbreak Reducing Tap Well

P925RTW

Product Data Sheets

15/25kV Deadbreak Copper Reducing Tap Well

Medium Voltage Catalog

Catalogs & Product Guides

Download a copy of our Medium Voltage Product Catalog for technical details and ordering information. If you don’t find what you are looking for, don’t hesitate to contact our team at the factory.